Tel: +353 61 240240 | Mobile: +353 86 8244488

PROFIBUS DP Slave

PROFIBUS DP Slave

The ComBricks PROFIBUS DP slave module has considerable added value for the installation. It is the only available device with a powerful 3-in-1 functionality: PROFIBUS DP slave device – ProfiTrace busmonitor – Modular repeater

SKU: 101-220210 Categories: ,

Description

The slave device enables the largest multiple cross gateways between PROFINET and PROFIBUS modules which are placed in the backplane. Simultaneously it permanently monitors the segment/network and acts as a repeater when it is used in combination with other communication modules.

Slave device (gateways and remote I/O)

It’s the component of choice to establish communication between multiple PROFINET and PROFIBUS controllers that manage their own specific network. The gateway works similarly to regular DP/DP and PN/DP couplers. The data area between the modules is customized with the help of pre-defined blocks from the GSD files. COMbricks has the advantage that 10 PROFINET / PROFIBUS modules can exchange information. The configuration steps are the same as any other PROFIBUS slave device. By means of the GSD file the respective I/O modules have to be selected in the configuration tool, after which the PLC can make the I/Os available for the software application and the network.

Repeater

The repeater works as any COMbricks PROFIBUS repeater. With the integrated ProfiTrace and the enhanced RS 485 signals it is the best partner you can get for extended and reliable segments.

Application areas

  • Coupling small machines
  • Linking networks with different controllers
  • Coupling PROFINET to PROFIBUS
  • Coupling PROFIsafe networks to regular networks
  • Migration from old control systems to new control systems
  • Quasi master-master communication

This product is UL-listed.


TECHNICAL SPECIFICATIONS

PROFIBUS Slave Device

  • DP-V0 (certification number: Z01776)
  • Ident Number: 696F
  • 9.6 kbps..12 Mbps (auto detect and including 45.45 kbps)
  • Bus address by dipswitches or set slave address command
  • 244 Bytes input and 244 bytes output (128 Bytes I/O per proxy)
  • Selectable number of I/O bytes: 1, 2, 3, 4, 8, 12, 16, 20, 24, 28, 32, 64 bytes
  • Fail safe: Outputs OFF, Outputs ON, Keep last value, Custom failsafe value
  • Simulation input patterns: ON, OFF, Blink, Up counter, Down counter, Zig Zag
  • Compatible partner/gateway modules: 101-220210, 101-220110, 101-210210, 101-210110, 101-210010
  • PROFIBUS DP Slave Device GSD filename: PROC696F.gsd (www.procentec.com/downloads)
  • Maximum number of gateway modules: 9
  • Words per gateway: 48, 64 words

Repeater

  • 1 RS 485 bus channel with DB9 connector
  • 31 devices/busloads per channel
  • 1200 m cable length (depends on baudrate)
  • No limit in cascading
  • RS-485 supported protocols: DP-V0, DP- V1, DP-V2, FDL, MPI, FMS, PROFIsafe, PROFIdrive and any other FDL based protocol
  • Data delay time: 2.0 TBit at 9.6 kbps .. 3 Mbps; 2.75 TBit at 6 Mbps; 3.75 Tbit at 12 Mbps
  • Delay time jitter: Max. ¼ Tbit

ProfiTrace Busmonitor

  • Live List
  • Statistics
  • Message recording

Backplane

  • 10 Networks (web server), 4 Networks (dipswitches and web server)
  • 10 Modules (positioned in the first 10 slots)
  • 390 mA current consumption
  • Power supply: provided through the backplane
  • Compatible backplane units: 101-200011, 101-200012, 101-200023, 101-200024, 101-200027
  • Backplane GSD filename: PROC696F.gsd (www.procentec.com/downloads)

Others

  • Operating temperature: 0..60 °C
  • Dimensions (LxWxH): 120 x 103 x 25 mm (without backplane)
  • Weight: 120 g
  • Head station firmware: 1.275 and higher
Go to Top