The ComBricks PROFINET Device enables the largest multiple cross gateway between other PROFINET and PROFIBUS modules which are placed in the backplane. Simultaneously, the PLC/DCS system that has the PROFINET Device in Data Exchange can access inserted I/O modules.
PROFINET IO Device
Description
The ComBricks PROFINET Device enables the largest multiple cross gateway between other PROFINET and PROFIBUS modules which are placed in the backplane. Simultaneously, the PLC/DCS system that has the PROFINET Device in Data Exchange can access inserted I/O modules.
It’s the component of choice to establish communication between multiple PROFINET and PROFIBUS controllers that manage their own specific network. The gateway works the same way as regular DP/DP and PN/DP couplers. The data area between the modules is customized with the help of some pre-defined blocks from the GSD files. ComBricks has the advantage that 10 PROFINET / PROFIBUS modules can exchange information.
The configuration steps are the same as any other PROFINET device. By means of the GSD file the respective I/O modules have to be selected in the configuration tool, after which the PLC can make the I/Os available for the software application and the network.
Application areas
- Coupling small machines.
- Linking networks with different controllers.
- Coupling PROFINET to PROFIBUS.
- Coupling PROFIsafe networks to regular networks.
- Migration from old control systems to new control systems.
- Quasi master-master communication.
- Virus / Hacker free PROFINET separator.
This product is UL-listed.
TECHNICAL SPECIFICATIONS:
PROFINET
- Version 2.25 – Conformance class B
- Certification number: ZZ10500
- Ident Number: 0x4000 hex – 0x0001 hex
- 1 ms – 1 .. 128 input or output bytes
- 1024 Bytes input and 1024 bytes output (204 Bytes per module)
- DeviceName by DCP or hardware rotary switch
- Transferrable bytes to proxies (inputs and outputs): 1, 2, 3, 4, 8, 12, 16, 20, 24, 28, 32, 64, 96, 128, 160, 192, 204
Ethernet
- 10/100 Mbps (100BaseTX, 10BaseT)
- Supported protocols: RT_CLASS_1, RTA, UDP, DCP, ARP, LLDP, SNMP (MIB II)
Connectors and cabling
- 2 Ports switch (RJ 45)
- 100 m cable length per switch port
- Switch delay time: ?? us
- Auto detect, Auto cross-over, Auto polarity
Backplane
- Not connected to the PB networks
- 10 Modules (positioned in the first 10 slots)
- 410 mA current consumption
- Power supply: provided through the backplane
- Compatible backplane units: 101-200011, 101-200012, 101-200023, 101-200024, 101-200027
- Compatible partner/gateway modules: 101-220210, 101-220110, 101-210210, 101-210110, 101-210010
Others
- Operating temperature: 0 .. 60 °C
- Dimensions (LxWxH): 115 x 100 x 25 mm (without backplane)
- Weight: 111 g
- Head station firmware: 1.264 and higher